Coding 2
General
(continued)
Coding in the factory setting
4B:0
51:0
52:0
52:0
53:0
54:0
6E:50
76:1
77:1
60
Function input lH: Room
thermostat (Vitotrol 100) for
constant temperature control
System with low loss header:
Boiler circuit pump is always
started when there is a heat
demand
Without flow temperature sensor
for low loss header
Without supply temperature
sensor for low loss header
Function connection sK of
the internal extension: DHW
recirculation pump
Without solar thermal system
No correction of measured
outside temperature
With LON communication module
(recognized automatically).
LON participant number
Vitocrossal 300 CU3A 26 to 57 Service
Possible change
4B:1
External demand.
4B:2
External blocking.
51:1
System with low loss header:
When there is heat demand, the
boiler circuit pump will only be
started if the burner is running.
Circulation pump is switched off
when run-on time expires.
51:2
System with heating water buffer
DHW tank:
When there is a heat demand, the
internal circulation pump will only
be started when the burner is
operational.
52:1
With flow temperature sensor
for low loss header (automatic
recognition).
52:1
With supply temperature sensor
for low loss header (automatic
recognition).
53:0
Central fault message
53:2
External heating circuit pump
(heating circuit 1).
53:3
External circulation pump for DHW
tank heating.
54:1
With Vitosolic 100 (automatic
recognition).
54:2
With Vitosolic 200 (automatic
recognition).
54:3
With solar control module SM1
without auxiliary function
(automatic recognition).
54:4
With solar control module SM1
with auxiliary function, e.g.
central heating backup (automatic
recognition).
6E:0
Outside correction in 0.1 K steps
to
0 to 49= -5 K to -0.1 K
6E:100
51 to 100= 0.1 K to 5 K
76:0
Without communication module
76:2
With cascade communication
module (recognized automatically;
only for constant temperature
control units).
77:2
LON participant number,
to
adjustable from 1 to 99:
77:99
1 = Boiler
10 - 98 = Vitotronic 200-H
99= Vitocom
Note: Allocate each number only
once.