Vitocrossal 300 CU3A 26 to 57 Service
General
(continued)
Coding in the factory set mode
Participant no.
Internal circulation pump function
51:0
77:1
Detached house/apartment building
7F:1
Lock out controls
8F:0
Set supply temperature for external demand
9B:70
Boiler
Coding in the factory setting
Single/multi boiler system
21:0
Service interval in months
23:0
Service status
24:0
System with low loss header:
Internal circulation pump always
starts when there is a heat
demand
LON participant number
Detached house
Operation in the standard menu
and extended menu enabled.
Note: The respective code is only
activated when you exit
the service menu.
Set supply temperature for
external demand 158°F (70°C)
No service interval (hours run)
selected
No time interval for burner
service
No "Service" display
Possible change
51:1
System with low loss header:
When there is a heat demand, the
internal circulation pump is only started
if the burner is operating.
Circulation pump is switched
off after a 60 sec. delay.
51:2
System with heating water
buffer DHW tank:
When there is a heat demand, the
internal circulation pump is only started
if the burner is operating.
Circulation pump is switched
off after a 60 sec. delay.
77:2
LON participant number,
to
adjustable from 1 to 99:
77:99
1 = Boiler
10 - 98 = Vitotronic 200-H
99= Vitocom
Note: Allocate each number only once.
7F:0
Apartment building
Separate adjustment of holiday program
and time program for DHW heating
possible.
8F:1
Operation in standard menu and
extended menu blocked.
Emissions test mode can be enabled.
8F:2
Operation enabled in the standard menu
and blocked in the extended menu.
Emissions test mode can be enabled.
9B:0
Set supply temperature for external
to
demand adjustable from 32 to 260°F
9B:127
(0 to 127°C) (limited by boiler-specific
parameters).
Possible change
21:1
Number of hours run before the burner
to
should be serviced is adjustable from
21:100
100 to 10,000 h
One adjusting step ≙ 100 h.
23:1
Interval adjustable from 1 to 24 months.
to
23:24
24:1
"Service" display (the address is
automatically set and must be manually
reset after a service has been carried
out).
Coding 1
51