Daikin ARC433A Series Troubleshooting Manual

Daikin ARC433A Series Troubleshooting Manual

Advertisement

Quick Links

Daikin Trouble Shooting Guide
Daikin Fault Codes
Indoor Fault Codes
Fault Code Definition
A0
External protection active
A1
Failure of indoor PCB
A3
High water level
A5
HP control in heating or freeze
protection in cooling
A6
Fan motor failure
A7
Failure of louvre motor
A8
Failure of power supply
A9
EEV failure
AF
High water level
AH
Failure of dust collector
AJ
Capacity setting error
C1
Communication failure. Between
main-sub PCB
C4
Indoor coil sensor
C5
Suction pipe sensor
C6
Failure of fan motor driver
C7
Front panel driving motor fault
C9
Return air sensor fault
CA
Discharge air sensor fault
CC
Failure of humidity sensor
CJ
Failure of remote sensor
Daikin Fault Codes
Outdoor Fault Codes
Fault Code Definition
E0
Protection devices tripped
E1
Failure of outdoor PCB
E3
High pressure
E4
Low pressure
E5
Inverter compressor lock
E5
Inverter compressor to hot
E6
DOL compressor locked
E7
Fan motor failure
E8
Inv compressor high current
E9
EEV motor failure
EA
4-way valve failure
EC
Inlet water temperature
EF
Thermal storage unit defect
F3
High discharge temperature
F6
High pressure in cooling
F6
Over charged
H0
Compressor sensor system
H1
Failure of humidifier damper
H3
Failure of hp switch
H4
Failure of lp switch
H5
Failure of compressor sensor
H6
Compressor position failure
H7
Failure of fan motor signal
H8
Compressor input error
H9
Failed ambient sensor
J1
Failed pressure sensor
J2
Failed current sensor
J3
Failed discharge pipe sensor
J4
Failed outdoor coil vapour sensor
J5
Failed suction pipe sensor
J6
Failed outdoor coil sensor
J7
Failed liquid pipe sensor
J8
Failed liquid pipe sensor
J9
Failed sub cool heat exchanger sensor Sensor open/short circuit
JA
Failed high pressure sensor
JC
Failed low pressure sensor
JH
Failed oil temperature sensor
www.climatecenter.co.uk
Supposed Causes
External protection wired to T1-T2 active
Defect of PCB or noise
Float switch open circuit
Poor airflow, short circuit, EEV, refrigerant charge,
indoor coil sensor incorrect value
Locked, over current, over load
Louvre motor/indoor PCB failed
Over current of AC input, defect of supply
Defect of EEV motor, indoor PCB
Float switch open circuit while thermo off
Defect of dust collecting element, PCB
Capacity setting adaptor missing
Failure of communication fan motor
control driver
Open/short circuit
Open/short circuit
Defect of fan motor sensor, control driver
Defect of limit switch, front panel driving motor
Return air sensor open/short circuit
Discharge air sensor open/short circuit
Failed humidity sensor
Defect of remote controller sensor
Supposed Causes
Outdoor safety device tripped
Defect of PCB or noise
High pressure switch tripped
Low pressure switch tripped
Inverter compressor locked
Compressor windings too hot
High current draw
Failed fan motor, PCB
Compressor, PCB
EEV motor, PCB
Defect of valve, PCB, sensor
Abnormal water temperature
Thermal storage EEV, PCB, sensor
Discharge temperature over 110°C
Detected by outdoor coil sensor
Refrigerant over charge
All sensors disconnected
Defect of limit switch/damper
High pressure switch open circuit
Low pressure switch open circuit
Defect of compressor overload sensor
Position detection error
Defect of fan motor, PCB
Defect of transistor, PCB, reactor
Sensor open short circuit
Pressure sensor failed
Defect of current sensor, PCB, compressor
Discharge pipe sensor open/short circuit
Sensor open/short circuit
Sensor open/short circuit
Sensor open/short circuit
Sensor open/short circuit
Sensor open/short circuit
High pressure sensor open/short circuit
Low pressure sensor open/short circuit
Open/short circuit
Past & Current Models
Split
Skyair
VRV
Split
Skyair
VRV
Package
Package

Advertisement

loading

Summary of Contents for Daikin ARC433A Series

  • Page 1 Daikin Trouble Shooting Guide Past & Current Models Daikin Fault Codes Indoor Fault Codes Fault Code Definition Supposed Causes Split Skyair Package External protection active External protection wired to T1-T2 active • • • Failure of indoor PCB Defect of PCB or noise •...
  • Page 2 Daikin Trouble Shooting Guide Past & Current Models Daikin Fault Codes Outdoor Fault Codes Fault Code Definition Supposed Causes Split Skyair Package Failure of inverter system Defect power transistor, inverter PCB • Failure of inverter PCB Blown fuse, defect of inverter PCB, fan motor •...
  • Page 3 Daikin Trouble Shooting Guide Past & Current Models Daikin Fault Codes System Fault Codes Fault Code Definition Supposed Causes Split Skyair Package Shortage of refrigerant Undercharged, EEV fault, faulty sensor • • • • Reverse or missing phase Reversed or missing phase •...
  • Page 4 Past & Current Models Fault Code Retrieval with Infra Red Remote Controller In the ARC433A series, the temperature display sections on the main unit indicate corresponding codes. 1. When the timer cancel button is held down for 5 seconds, a “00” indication flashes on the temperature display section.