U-Line 3018RGL User Manual page 69

Safety • installation & integration • operating instructions • maintenance • service 18" glass door refrigerator 3000 series
Hide thumbs Also See for 3018RGL:
Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
NOTICE
Customer care MUST be notified and approve of
any changes to the differential before they are
made. Failure to notify customer care will void
the warranty.
Offsets are used to adjust or correct thermistor readings.
Offset values are added to the current thermistor reading
and are then used by the control board to determine
cooling and defrost cycle times. Offsets have a range of
+/- 10°F. Corrected values may be viewed through the
customer "All Temps" menu or TTY output.
To access Offsets
1. Use Down
to select "Offsets".
2. Press Select
.
3. Use Up
and Down
thermistors.
To change offset
1. Press Select
, the selected thermistor will begin to
flash.
2. Use Up
or Down
3. Press Select
to confirm setting.
To exit the Offset menu use Up
Menu" and press Select
to scroll through available
to modify offset value.
to select "Return to
to confirm.
Self Test
Up
Down
Self test is used to initiate a self diagnostic report. Any
system faults will be displayed under Self test. If no errors
are present "no errors" will be displayed and the main
control board is functioning properly. If an error is listed
attempt to correct it before changing control board. See
troubleshooting for tips on correcting errors.
To access Self Test
1. Use Down
to select "Self Test".
2. Press Select
.
3. Use Up
and Down
information.
To exit the Self Test use Up
and press Select
to confirm.
Differentials
Up
Can be displayed in Celsius
Down
NOTICE
Customer care MUST be notified and approve of
any changes to the differential before they are
made. Failure to notify customer care will void
the warranty.
u-line.com
Select
RETURN TO MENU
SELF TEST
NO ERRORS
try "RELAY TOGGLE"
to scroll through available
to select "Return to Menu"
Select
RETURN TO MENU
DIFFERENTIALS
ZONE = 1°F
Service Mode 5