Download Print this page

Manitowoc GR-0400A Procedure Manual page 2

Refrigerant field conversion procedure
Hide thumbs Also See for GR-0400A:

Advertisement

CONVERSION INSTRUCTIONS
1. Recover R-502 refrigerant from the ice machine in accordance with local and national governing laws.
2. Refer to "Equipment Modification Requirements" checklist on previous page.
3. Remove and replace liquid line filter drier. Use only Manitowoc approved OEM filter drier, P/N 8930233.
NOTE: compressor oil does not require changing.
4. Evacuate the ice machine. IMPORTANT: remote models require a 4-point hose hookup to evacuate
properly (refer to service manual or service bulletin, SB-18-84, for proper evacuation procedure).
5. Charge ice machine with R-402B refrigerant. System charge is identical to R-502 charge listed on
model/serial number tag. NOTE: charge with liquid only into the high side of the ice machine using
weigh-in method or "Dial-A-Charge" (refer to service manual or service bulletin, SB-18-84, for proper
charging procedure).
6. Remove purple R-502 label near service valves. Do not remove model and serial number tags!
7. Attach an R-402B conversion label, P/N 8134423, to each of the two locations:
A. Next to the serial number plate.
B. Next to the service valves.
IMPORTANT: write service company name and conversion date on each label.
8. Restart ice machine and verify it operates properly (refer to service manual, if necessary). Water-cooled
models maintain head pressure at the same R-502 setting.
8010513
Sheet 2 of 2
08/96

Advertisement

loading
Need help?

Need help?

Do you have a question about the GR-0400A and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Gr-0401wGr-0490nGd-0402aGd-0403wGd-0492nGy-0404a ... Show all