Frico SIReFAEMX Original Instructions Manual page 13

Sire advanced fan heater electric
Table of Contents

Advertisement

Temperature control without mixing
cabinet (fan mode Thermostat /Automatic
fan):
Comfort
1. Fan starts at set setpoint value.
2. Heating on at set setpoint value – 0.5K
Eco
Fan starts at set setpoint value - 1K.
Heating on at set setpoint value – 2K.
Heating off at set setpoint value.
Temperature control (Outlet temp. limit)
with mixing cabinet (fan mode Thermostat/
Automatic fan):
Comfort
1. Increases heating step.
2. Gradually closes damper to night mode.
Eco
1. Gradually closes damper to night mode.
2. Increases heating step.
Heating step diff.
The temperature difference between
connection of the electrical heating step.
Factory setting of 1.0 and a set point value of
20°C gives the following function: low output
step cuts in at +19.5°C (cuts out at +20.0°C).
If the temperature continues to fall below
+18.5°C another output step cuts in (cuts
out at +19.0°C). For 3 output steps the last
step is engaged at +17.5°C and switches off at
+19.0°C.
>Installer menu>Heating settings
Eco / Comfort
Heating step diff.
Heating step limit
Factory setting
Heating step diff: 1.0 K (0 K – 10 K)
Heating step limit
Possibility of limiting the heating.
>Installer menu>Heating settings
Heating step diff.
Heating step limit
Sensor calibration
SIRe Advanced Fan Heater Electric
>Installer menu>Heating settings
Heating step diff.
1.0 K
>Installer menu>Heating settings
Heating step limit
2
Factory setting
Heating step limit: 2 (SE06-15, 20) 3 (SE30)
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
>Installer menu>Heating settings
Heating step limit
Sensor calibration
Stepless heat control
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)
Outdoor temperature sensor: 0.0 K (-10 K –
10 K)
Stepless heat control
For stepless control of electrical heating, for
example via external triac.
>Installer menu>Heating settings
Sensor calibration
Stepless heat control
Control range limit
Factory setting
Stepless heat control: ON (Off - not
selectable)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
>Installer menu>Heating settings
Sensor calibration
Stepless heat control
Control range limit
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
GB
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
0.0 K
>Installer menu>Heating settings
Stepless heat control
ON
>Installer menu>Heating settings
Control range limit
35°C
33