Heat & Glo 6000C-IPI Owner's Manual page 28

Hide thumbs Also See for 6000C-IPI:
Table of Contents

Advertisement

Top Vent - Vertical Termination
No Elbow
V
= 40 ft. Max. (12.4 m)
1
V
= 3 ft. Min. (914 mm)
1
Note: If installing a vertical vent/
termination off the top of the ap-
pliance, the fl ue restrictor should
be used.
Figure 7.6
28
V
1
Heat & Glo • 6000C-IPI, 8000C-IPI • 2164-900 Rev. AB • 10/15
Flue Restrictor Instructions
1. Remove exhaust shield using a 1/4 inch nut driver by
removing the three screws securing it in place (see
Figure 7.7).
2. Orientate and align the two pieces of the fl ue restrictor
as shown in Figure 7.9.
EXHAUST
SHIELD
FLUE
RESTRICTOR
INSTALLED
Figure 7.7
3. Match the amount of vertical you have in the system
with the chart to fi nd the appropriate position to set the
fl ue restrictor. See Figure 7.8 and 7.9.
4. Center the two fl ue restrictor pieces on the vent at the
setting selected in step 3 and secure in place by using
two self-tapping screws. See Figure 7.7.
5. Reinstall the exhaust shield.
TOP VENT
Vertical
NG
4 ft.
1-1
Restrictor
8 ft.
2-2
15 ft.
3-3
20 ft.
3-4
25 ft.
3-4
30 ft.
4-4
35 ft.
4-4
40 ft.
4-4
Figure 7.8
REAR VENT
LP
NG
LP
No
No
No
Restrictor
Restrictor
No
1-2
1-1
Restrictor
3-2
2-2
1-2
3-3
3-3
2-3
3-3
3-3
2-3
3-4
3-4
3-3
3-4
3-4
3-3
4-4
4-4
3-4