Managing cables

Attention: The minimum bend radius should be no smaller than 10x the cable
radius. The minimum bend radius for a 50 micron cable is 5 cm (2 in.) under full
tensile load and 3 cm (1.2 in.) with no tensile load.
Note: Contact your IBM representative for options regarding different cable and
Cable management recommendations:
v Leave at least 1 m (3.28 ft) of slack for each port cable. This provides room to
v If ISL Trunking is in use, group the cables by trunking group. The ports are
v Use only hook-and-loop fasteners for securing optical cables. Do not use cable
v For easier maintenance, label the fiber optic cables and record the devices to
v Use the cable management fingers attached to the rack rails to organize the
v Keep LEDs visible by routing port cables and other cables away from the LEDs.
For the procedure to install the ICL cables see "Removing and replacing
inter-chassis link (QSFP) cables" on page 95.

Verifying correct operation and backing up the configuration

To verify correct operation and to back up the system, follow these steps.
1. Check the LEDs to verify that all components are functional. For information
2. If necessary, log on to the switch by Telnet, using the admin account.
3. Verify the correct operation of the system by entering the switchShow
4. Verify the correct operation of the SAN768B-2 in the fabric by entering the
5. To back up the configuration, run the following two steps:
6. Run the following commands to see additional configuration information that
42
SAN768B-2 Installation, Service, and User Guide
patch panel configurations to simplify cable management with higher
density FC8-64 port blades.
remove and replace blades in the chassis, allows for inadvertent movement of
the rack, and helps prevent the cables from being bent to less than the minimum
bend radius.
color-coded to indicate which ports can be used in the same ISL Trunking group:
eight ports marked with solid black ovals alternate with eight ports marked with
oval outlines.
ties. They can be easily overtightened and can damage the optical cables.
which they are connected.
cables off to the side of the chassis, and away from the chassis exhaust vents.
about LED patterns, see Chapter 4, "Monitoring system components," on page
45.
command from the workstation. This command provides information about
switch and port status.
fabricShow command from the workstation. This command provides general
information about the fabric.
a. Enter the configupload -vf command. This command uploads the system
virtual fabric data.
b. Enter the configupload command. This command uploads the system
configuration.
you can then copy to a file to save:
v configShow
v ipAddrShow