Bradford White UCG100H199 Installation & Operation Manual page 12

Gas-fired commercial water heater
Table of Contents

Advertisement

The draft hood relief opening of the water heater and combustion air inlet must be in the same atmospheric pressure
zone. Large exhaust fans in kitchens and other locations can lower the air pressure inside an enclosure and interfere
with the proper operation and venting of the water heater. In these cases, the water heater should be installed in a
separate room with the combustion and ventilation air supplied directly from outdoors as previously described.
1. If the openings communicate directly with an additional room(s) of sufficient volume, each opening must have a
minimum free area opening of 1 in.
appliances in the confined space, but not less than 100 in.
2. If the openings communicate with the outdoors through horizontal ducts, each opening must have a minimum free
2
area of 1 in.
/2000 BTU (2.54cm
3. If the openings communicate directly with the outdoors or through vertical ducts with the outdoors, each opening must
have a minimum free area of 1 in.
the enclosure.
ALL AIR FROM INSIDE THE BUILDING
The confined space must be provided with two permanent openings communicating directly with an additional room(s) of
sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of
all gas utilization equipment installed in the combined space must be considered in making this determination. Each
opening must have a minimum free area of 1 in.
utilization equipment in the confined space, but not less than 100 square inches (254cm
12 inches (30.5 cm) of the top and one within 12 inches (30.5 cm) of the bottom of the enclosure.
UNCONFINED SPACES
In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue
gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.), additional air may need to be provided using the methods described above under CONFINED SPACES: All
Air From Outdoors or SPECIALLY ENGINEERED INSTALLATIONS.
SPECIALLY ENGINEERED INSTALLATIONS
The requirements noted under CONFINED SPACES above must not necessarily govern when special engineering,
approved by the authority having jurisdiction, provides an adequate supply of air for combustion, ventilation, and dilution
of flue gases.
CHEMICAL VAPOR CORROSION
Corrosion of the flue ways and vent system will occur if air for combustion contains certain chemical vapors. Such
corrosion may result in poor combustion and create a risk of asphyxiation, as well as reducing the life of the water
heater.
Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool
chemicals, calcium and sodium chloride, waxes and process chemicals are corrosive. Products of this sort should not
be stored near the water heater or outside by the air intake (if applicable).
CAUTION
2
2
/1000 BTU (2.54cm
2
/0.59kW) per hour of the total rating of all gas appliances in the enclosure.
2
2
/4000 BTU (2.54cm
/1.18kW) per hour of the total rating of all gas appliances
2
/1000 BTU (2.54cm
12
/0.29kW) per hour of the total input rating of all gas
2
2
(254 cm
).
2
/0.29kW) per hour of the total input rating of all gas
2
). One opening must be within
in

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ucg100h270Ucg100h399

Table of Contents