Sinclair AMC-15A Service Manual page 28

Mobile series
Hide thumbs Also See for AMC-15A:
Table of Contents

Advertisement

Room temp sensor
Compressor
Excessive noise.
Copper tubing
Water tank full
Water depth sensor if failure
Water depth is over load in
Water full alarm
chassis
Water depth sensing
structure
Air filter
Air discharge pipe
Unit undersized
Condenser and Evaporator
Circulation in condensing
water
Fan motor
Cooling or heating
Air flow
feels not good
Less refrigerant
Capillary tube
Compressor
Heat sources
No power
Wiring
Temperature setting
Mode setting
No cooling or
Compressor
heating.
Electric heater failure
Over heat fuse failure
Main PCB
Power supply
The unit starts and
Main PCB
stops frequently.
Room temperature
Sudden change of
temperature units
from °C to °F and
vice versa
27
Check the temperature setting if not at the coolest (in cooling
mode) or the warmest (in heating mode). Set it if not.
Check the compressor for open circuit or ground. If open or
grounded, replace the compressor.
Remove the cabinet and carefully rearrange tubing not to
contact cabinet, compressor, shroud and barrier.
Check and pour if the water tank is full.
Check and replace if failure.
Check and drainage the water in the chassis by open the
drainage hose on the chassis.
Check and replace or realign if the structure is failure.
Clean or replace if restricted.
Realign and assemble if the installation of the air discharging
pipe failure. Replace if damaged.
Determine if the unit is properly sized for the area to be cooled
or heated.
Clean or replace if restricted.
To check wether water motor damaged or water hose is block or
not
Check the fan capacitor and replace if not within +/-10% of
manufactures rating.
Clean or remove if any barrier is found to block the inlet/outlet
wind flow of the unit.
Check the tubes for reasons of leakage. Recycle the refrigerant,
correct the leakage points and recharge.
Regulate the flow if capillary tube and make the evaporating
temperature appropriate if the evaporator is frosted. Replace if
blocked. Repair joint if leaking.
The inlet and outlet valve of the compressor is damaged,
making the low pressure connected with the high pressure. The
refrigerating system can not produce high pressure and low
pressure. Replace the compressor after checking for the reason.
Reduce if too many.
Check the voltage. Call an electrician if no within the limit.
Check the terminals. Repair and correct if loose.
Check and adjust the temperature setting.
Check and adjust the mode setting.
Check and replace if the compressor, the over-load protector or
wiring is broken.
Check and replace if the heater is damaged.
Check and replace if the fuse is damaged.
Check the voltage of main PCB. Replace the main PCB when
the unit failure in heating mode.
The input power supply voltage is too low. Call an electrician if
not within limits.
Check and replace the main PCB if the compressor relay on
PCB is shorted or damaged.
When the room temperature is too high, the compressor will
protect.
Solution: switching the units from °F to °C and viceversa
Procedure: Please switch off the unit to "STAND-BY"
mode by pressing the button "POWER" on the unit (the unit is
plugged in), hold for 5-10 seconds button "FUNC" on the unit
and after a beep sound switch on the unit by button "POWER".
Trouble shooting