Section 3. Unit Preparation - Trane 4TTR3018–060 Installer's Manual

Condensing units
Hide thumbs Also See for 4TTR3018–060:
Table of Contents

Advertisement

2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
Do not locate close to bedrooms as operational
sounds may be objectionable.
Position the outdoor unit a minimum of 12" from
any wall or surrounding shrubbery to ensure
adequate airflow.
Outdoor unit location must be far enough away
from any structure to prevent excess roof runoff
water from pouring directly on the unit.
2.4 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory sup-
plied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.

Section 3. Unit Preparation

3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report prompt-
ly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet,
remove tabs by cutting with a sharp tool.
4
Avoid Install
Near Bedrooms
Min. 12" to
Shrubbery
Min. 12" to
Shrubbery
Min 5' Unrestricted
Min 3'
Unrestricted
Access Panel
Min. 12"
to Wall
18-AC79D1-6-EN