Trane 4TTR3018–060 Installer's Manual

Trane 4TTR3018–060 Installer's Manual

Condensing units
Hide thumbs Also See for 4TTR3018–060:

Advertisement

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT - This Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser's purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture's split
systems are A.H.R.I. rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and
outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

Table of Contents

Section 1. Safety ..................................................................................... 2
Section 2. Unit Location Considerations.............................................. 3
Section 3. Unit Preparation .................................................................... 5
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 6
Section 6. Refrigerant Line Routing ..................................................... 7
Section 7. Refrigerant Line Brazing ...................................................... 8
Section 8. Refrigerant Line Leak Check ............................................. 10
Section 9. Evacuation ........................................................................... 11
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up .............................................................................. 17
Section 14. System Charge Adjustment ............................................. 18
Installer's Guide
Condensing Units
4TTR3018-060
18-AC79D1-6-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane 4TTR3018–060

  • Page 1: Table Of Contents

    18-AC79D1-6-EN Installer’s Guide Condensing Units 4TTR3018–060 ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa- tion pack upon completion of work. These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation.
  • Page 2: Section 1. Safety

    Section 1. Safety WARNING WARNING LIVE ELECTRICAL COMPONENTS! This information is intended for use by individuals During installation, testing, servicing, and trouble- possessing adequate backgrounds of electrical and shooting of this product, it may be necessary to work mechanical experience. Any attempt to repair a central with live electrical components.
  • Page 3: Section 2. Unit Location Considerations

    Section 2. Unit Location Considerations 2.1 Unit Dimensions and Weight Table 2.1 Unit Dimensions and Weight Models H x D x W (in) Weight* (lb) 4TTR3018H 29 x 26 x 29 4TTR3024H 29 x 26 x 29 4TTR3030G 29 x 30 x 33 4TTR3036G 29 x 30 x 33 4TTR3042D...
  • Page 4: Section 3. Unit Preparation

    2.3 Suggested Locations for Best Reliability Ensure the top discharge area is unrestricted for Avoid Install at least five (5) feet above the unit. Near Bedrooms Three (3) feet clearance must be provided in front of the control box (access panels) and any Min 5’...
  • Page 5: Section 4. Setting The Unit

    4TTR3060D 5.2 Factory Charge Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant charge adjustment is necessary.
  • Page 6: Section 6. Refrigerant Line Routing

    5.4 Refrigerant Line Insulation Important: The Vapor Line must always be Vapor Line insulated. DO NOT allow the Liquid Line and Liquid Line Insulation Vapor Line to come in direct (metal to metal) contact. 5.5 Reuse Existing Refrigerant Lines CAUTION If using existing refrigerant lines make certain that all joints are brazed, not soldered.
  • Page 7: Section 7. Refrigerant Line Brazing

    8 Feet Maximum Wall Isolator Line Set 8 Feet Maximum Side View Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly to Vapor Line using tape, wire, or other appropriate method every 8 ft. Isolation In Wall Spaces Wall Sealant Ductwork...
  • Page 8 STEP 2 - Remove the pressure tap cap and valve cores from both service valves. STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen. STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
  • Page 9: Section 8. Refrigerant Line Leak Check

    STEP 5 - Replace the pressure tap valve cores after the service valves have cooled. Section 8. Refrigerant Line Leak Check 8.1 Check For Leaks STEP 1 - Pressurize the refrigerant lines and 150 PSIG evaporator coil to 150 PSIG using dry nitrogen. STEP 2 - Check for leaks by using a soapy solu- tion or bubbles at each brazed location.
  • Page 10: Section 9. Evacuation

    Section 9. Evacuation 9.1 Evacuate the Refrigerant Lines and Indoor Coil Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete. 0350 Microns STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
  • Page 11: Section 11. Electrical - Low Voltage

    10.1 Open the Liquid Service Valve WARNING Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Unit Side 3/16” Hex Wrench Failure to follow this warning will result in abrupt of Service release of system charge and may result in Valve...
  • Page 12 11.2 Low Voltage Hook-up Diagrams With TEM 3, 4, 6 With TAM 4, 5, 7 Outdoor Outdoor Thermostat Air Handler Thermostat Air Handler Unit Unit 24 VAC HOT 24 VAC HOT 24 VAC 24 VAC Common Common Blue Blue COOL/HEAT COOL/HEAT 1st STAGE 1st STAGE...
  • Page 13: Section 12. Electrical - High Voltage

    Section 12. Electrical - High Voltage 12.1 High Voltage Power Supply WARNING LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be nec- essary to work with live electrical components. Failure to follow all electrical safety precau- tions when exposed to live electrical compo- nents could result in death or serious injury.
  • Page 14: Section 13. Start Up

    Section 13. Start Up 13.1 System Start Up STEP 1 - Ensure Sections 7 through 12 have been completed. STEP 2 - Set System Thermostat to OFF. DONE CANCEL STEP 3 - Turn on disconnect(s) to apply power to the indoor and outdoor units. STEP 4 - Wait one (1) hour before starting the unit if compressor crankcase heater acces- sory is used and the Outdoor Ambient is below...
  • Page 15: Section 14. System Charge Adjustment

    Section 14. System Charge Adjustment 14.1 Temperature Measurements STEP 1 - Check the outdoor temperatures. 120º F Subcooling (in cooling mode) is the only recom- mended method of charging above 55º F ambi- ent outdoor temperature. 55º F Outdoor Temp For best results the indoor temperature should be kept between 70º...
  • Page 16 STEP 2 - Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below. 1 1/2 Ton 2 Ton SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) Add 3°...
  • Page 17 STEP 4 - Measure the liquid line temperature and pressure at the outdoor unit’s service valve. Measured Liquid Line Temp = __________ º F Liquid Gage Pressure = __________ PSI Final Subcooling Value = __________ º F 107 °F STEP 5 - Use the final subcooling value, refriger- Table 14.2 ant temperature and pressure from STEP 4, to R-410A REFRIGERANT CHARGING CHART...
  • Page 18 STEP 6 - Adjust refrigerant level to attain proper gage pressure. Add refrigerant if the Liquid Gage Pressure is lower than the chart value. 1. Connect gages to refrigerant bottle and unit as illustrated. 2. Purge all hoses. 3. Open bottle. 4.
  • Page 19: Section 15. Checkout Procedures And Troubleshooting

    STEP 9 - Record System Information for refer- ence. Record system pressures and temperatures after charging is complete. Measured Suction Line Temp = __________ º F Outdoor model number = _________________ Liquid Gage Pressure = __________ PSI Measured Outdoor Ambient = __________ º F Measured Indoor Ambient = __________ º...
  • Page 20: Troubleshooting

    The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. 6200 Troup Highway Representative-only illustrations included in this document. Tyler, TX 75707 www.trane.com © 2014 Trane U.S.,Inc. 12/14 18-AC79D1-6-EN...