Trane 4TTR3018–060 Installer's Manual page 18

Condensing units
Hide thumbs Also See for 4TTR3018–060:
Table of Contents

Advertisement

STEP 6 - Adjust refrigerant level to attain
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure
is lower than the chart value.
1. Connect gages to refrigerant bottle
and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pres-
sure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condi-
tion to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent
leaks. Tighten finger tight plus an ad-
ditional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Tables in the Service
Facts to verify typical performance.
18
20 MIN.
(Example only - see Service Facts)
PRESSURE CURVES FOR 4TTR3036D1000A
4TXCB036BC3
Cooling with Thermal Expansion Valve
550
INDOOR ENTERING
WET BULB CURVES
500
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
450
400
350
(3)
(4)
300
250
(1)
200
40
50
60
70
80
OUTDOOR TEMPERATURE (Degree F)
170
INDOOR ENTERING
165
WET BULB CURVES
160
TOP TO BOTTOM
155
71, 67, 63 AND 59 DEG F.
150
145
140
(5)
(3)
135
130
125
120
115
110
105
(1)
100
40
50
60
70
80
90
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
ACTUAL:
(4) LIQUID PRESSURE @ 1060 CFM IS 318 PSIG
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 1060 CFM IS 133 PSIG
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
INTERCONNECTING LINES
GAS - 3/4 " O.D.
LIQUID - 3/8 " O.D.
(2)
90
100
110
120
(2)
100
110
120
18-AC79D1-6-EN