Electrical Parts Specifications - Mitsubishi Electric PUHZ-RP250YHA2 Service Manual

Outdoor unit
Hide thumbs Also See for PUHZ-RP250YHA2:
Table of Contents

Advertisement

5-4. ELECTRICAL PARTS SPECIFICATIONS

Outdoor unit
Parts name
FUSE
(FUSE1,2)
FUSE
(F 3,4)
Valve
4-way Valve Coil
21S4
Linear Expansion
Valve
Linear Expansion
Valve Coil
(LEV-A)(LEV-B)
Bypass Valve
Bypass Valve Coil
(SV)
Reactor
(DCL)
High pressure switch
(63H1)
High Pressure
Switch
(63H, 63H2)
Low Pressure
Switch
(63L)
Fan Motor
(MF1)(MF2)
Thermistor
(Outdoor Pipe)
(TH3)
Thermistor
(Discharge)
(TH4)
Thermistor
(Outdoor2-PhasePipe)
(TH6)
Thermistor
(Outdoor)
(TH7)
(Power Supply)
(TB1)
(Indoor / Outdoor)
(TB2)
Main Smoothing Capacitor
(CB1, CB2)
Rush Current
Protect Resister
(RS)
Compressor
(MC)
PUHZ-RP200YHA2
UKV-32D
(0~480 Pulse)
PUHZ-RP250YHA2
250V 15A
250V 6.3A
STF0731Z
STF AC220~240V
(BG50T388)
DC12V
FDF6A-008-RK
FQ
AC220~240V
2.7mH 25A
OFF 4.14±0.1MPa / ON 3.14±0.15MPa
OFF 3.60 + 0.2MPa
ON 2.80 ± 0.15MPa
OFF -0.03 ± 0.03MPa
ON
8P 150W
2
SIC-81FW-D8187
5P
(L1, L2, L3, N,
)
3P
(S1, S2, S3)
2200
400V
ANB52FFJMT
Scroll type 6P
10
HAM-BD35
(0~480 Pulse)
ACB-1UB24
0.05 ± 0.04MPa