5

DATA

5-1. ADJUSTING THE AMOUNT OF REFRIGERANT

Permitted
Outdoor unit
pipe length
RP200
120m or less
RP250
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
Main piping:
Amount of additional
Liquid line size
=
charge [kg]
12.7 over all length [m]
0.12 [kg/m]
Additional charge amount
RP200 3.6 kg
for 70 m
RP250 4.8 kg

5-2. COMPRESSOR TECHNICAL DATA

Unit
PUHZ-RP200, 250YHA2
Compressor model
U-V
Winding
U-W
Resistance
(
)
W-V

5-3. NOISE CRITERION CURVES

MICROPHONE
1m
1.5m
Initial charge
(kg)
30 m and less
31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less
6.5
No additional
charge necessary
7.1
Main piping:
Liquid line size
+
9.52 overall length [m]
0.09 [kg/m]
ANB52FFJMT
0.30
0.30
0.30
UNIT
GROUND
Amount of additional refrigerant charge (kg)
0.9 kg
1.8 kg
1.2 kg
2.4 kg
Branch piping: Liquid
line size
+
+
9.52 overall length [m]
0.06 [kg/m]
PUHZ-RP200YHA2
PUHZ-RP250YHA2
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63
125
BAND CENTER FREQUENCIES, Hz
9
71-120 m and less
The additional charge
2.7 kg
3.6 kg
amount is obtained by
3.6 kg
4.8 kg
the following formula.
Branch piping: Liquid
line size
3.6 (kg)
6.35 overall length [m]
0.02 [kg/m]