Mitsubishi Electric PUHZ-RP250YHA2 Service Manual page 43

Outdoor unit
Hide thumbs Also See for PUHZ-RP250YHA2:
Table of Contents

Advertisement

Symptoms: Nothing is displayed on the remote controller
Diagnosis flow
Check the voltage of the
terminal block (TB6) of
the remote controller.
DC 10V to DC 16V?
NO
Check the status
of the LED2.
Blinking
Check the status of the LED2
after disconnecting the remote
controller wire from the terminal
block (TB5) of the indoor unit.
Check the status
of the LED2.
Blinking
YES
Lighting
Lighting
43
LED display of the indoor
controller board
LED1 :
LED2 :
LED3 : —
Inspection method and
Cause
troubleshooting
• Defective
• Replace the
remote controller
remote controller.
• Breaking or poor
• Check if there is breaking
contact of the remote
or poor contact of the
controller wire
remote controller wire.
Check the voltage of the
terminal block (TB5)
connecting the remote
controller wire.
If it is not between DC 10V
and DC16V, the indoor
controller board must be
defective.
• The remote controller
• Check if the remote
wire short-circuits
controller wire is
short-circuited.
• Defective indoor
• Replace the indoor
controller board
controller board.
or