[ III Specification ]

2. Electrical parts specifications

model
Parts name
Outlet air temperature
thermistor
Liquid pipe thermistor
Gas pipe thermistor
Inlet air temperature
thermistor
Fuse
Fan motor
(with inner thermostat)
Linear expansion valve
Power supply terminal
bed
Transmission terminal
bed
HWE1804A
Symbol
PEFY-P36, 48NMHU-E-OA
TH21
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
TH22
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
TH23
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
TH24
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
FUSE
8-pole, output 244W
MF1, 2
SIC-101CW-D8244-4
LEV
TB2
TB5
TB15
PEFY-P72NMHU-E-OA
250 VAC 6.3A
10-pole, output 375W
KMUC4E2MW or KMUC4E3MW
12 VDC Stepping motor drive
(L, N,
) 250V 20A
(M1, M2, S) 250V 20A
(1, 2) 250V 15A