[1] Cautions for service

(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.

[2] Additional refrigerant charge

When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

[3] Service tools

Use the below service tools as exclusive tools for R410A refrigerant.
No.
Tool name
Gauge manifold
Charge hose
Electronic scale
Gas leak detector
Adaptor for reverse flow check
Refrigerant charge base
Refrigerant cylinder
Refrigerant recovery equipment
Gravimeter
·Only for R410A
·Use the existing fitting specifications . (UNF1/2)
·Use high-tension side pressure of 5.3MPa·G or over.
·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
·Use the detector for R134a, R407C or R410A.
·Attach on vacuum pump.
·Only for R410A
·Top of cylinder (Pink)
·Cylinder with syphon
4
Unit
Specifications