Electrical Parts Specifications - Mitsubishi Electric CITY MULTI PEFY Series Technical & Service Manual

Air-conditioners for building application, ceiling concealed, indoor unit
Hide thumbs Also See for CITY MULTI PEFY Series:
Table of Contents

Advertisement

SPECIFICATION-Electrical parts specifications

3-2. Electrical parts specifications

Model
Symbol
Parts name
Tranrsformer
T
Room temperature
TH21
thermistor
Liquid pipe
TH22
thermistor
Gas pipe thermistor
TH23
Fuse
(Indoor controller
FUSE
board)
Fan motor
(with
MF1, 2
Output130W
Innerthermostat)
Innerthermostat
(Fan motor)
Fan motor capacitor
C1
Linear expansion
( 0~1800pulse
LEV
valve
Power supply
TB2
terminal bed
TB5
Transmission
terminal bed
TB15
Drain pump
DP
Drain sensor
DS
HWE1212A
PEFY-
PEFY-
PEFY-
P15
P18
P24
NMHU-E2
NMHU-E2
NMHU-E2
(Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)
Resistance 0°C [32°F]/15kΩ, 10°C [50°F]/9.6kΩ, 20°C [68°F]/6.3kΩ, 25°C [77°F]/5.4kΩ,
Resistance 0°C [32°F]/15kΩ, 10°C [50°F]/9.6kΩ, 20°C [68°F]/6.3kΩ, 25°C [77°F]/5.4kΩ,
Resistance 0°C [32°F]/15kΩ, 10°C [50°F]/9.6kΩ, 20°C [68°F]/6.3kΩ, 25°C [77°F]/5.4kΩ,
4-pole
4-pole
4-pole
Output130W
Output180W
NC-45VMS
NC-45VMS
NC-71VMS
4μF×440V
4μF×440V
5μF×440V
DC12V Stepping motor drive
port dimension ø 3.2
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>)
Disconnect the connector, and measure the resistance using a tester.
PEFY-
PEFY-
P27
P30
NMHU-E2
NMHU-E2
30°C [86°F]/4.3kΩ, 40°C [104°F]/3.0kΩ
30°C [86°F]/4.3kΩ, 40°C [104°F]/3.0kΩ
30°C [86°F]/4.3kΩ, 40°C [104°F]/3.0kΩ
250V 6.3A
4-pole
4-pole
Output190W
Output190W
NC-90VMS-W
NC-90VMS-W
OFF 135ºC ±5ºC ON 86ºC ±15ºC
8μF×440V
10μF×440V
DC12V Stepping motor drive
port dimension ø 5.2
( 0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>)
(L1, L2, G) 250V 20A
(M1, M2, S) 250V 20A
(1, 2) 250V 15A
(Ambient temp.: 20ºC)
Normal
Abnormal
399Ω
Open or short circuit
0°C/6.0kΩ,10°C/3.9kΩ
20°C/2.6kΩ,25°C/2.2kΩ
30°C/1.8kΩ,40°C/1.3kΩ
9
PEFY-
PEFY-
PEFY-
P36
P48
P54
NMHU-E2
NMHU-E2
NMHU-E2
4-pole
4-pole
4-pole
Output400W
Output400W
Output400W
NC-112VMS-W
NC-112VMS-W
NC-112VMS-W
11μF×440V
11μF×440V
11μF×440V
DC12V Stepping
motor drive port
dimension ø 6.4
( 0~1800pulse
<at R410A
outdoor unit>
0~2000pulse
<at the other
outdoor unit>)