12.5
Force Heater Mode Operation
The backup heater also serves as backup in case of malfunctioning of the Monobloc unit.
1
Make sure the OFF/ON control panel LED is OFF (no operation).
2
Press the Force button to start the force heater mode operation.
3
During force heater mode, all other operations are not allowed.
4
Press OFF/ON button to stop the force heater mode operation.
12.6
Monobloc Unit Safety
12.6.1 Monobloc Unit Safety Control
1
When water pump is ON, the system will start checking flow switch status (ON/OFF).
2
If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3
After water pump OFF for more than 10 minutes, it will be ON back and the Monobloc unit safety control
checking is restarted.
12.7
Auto Restart Control
1
When the power supply is cut off during the operation of Monobloc unit, the compressor will re-operate after
power supply resumes.
61