Panasonic WH-MDC09C3E8 Service Manual page 50

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MDC09C3E8:
Table of Contents

Advertisement

12.1.5 Cool + Tank Mode Operation
12.1.6 Tank Mode Operation
Control contents:
3 ways valve direction
- 3 ways valve switch and fix to tank side.
Heatpump Thermostat characteristic
- Water set temperature = tank set temperature or [55°C] whichever lower.
- Heatpump Water Outlet set temperature is set to Maximum (55°C) at tank mode
i. Case 1
- THERMO OFF TEMP:
1
THERMO OFF TEMP = Water set temperature + [+2°C].
2
Tank temperature > THERMO OFF TEMP for continuous 3 minutes, heatpump OFF and water pump OFF.
- THERMO ON TEMP:
1
THERMO ON TEMP = Water set temperature + [-3°C].
2
When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minute then heatpump ON.
- Pump ON when Tank temperature is less than tank temperature when Heatpump Thermo Off - [-3°C].