16.5.26 Indoor Water Inlet Temperature Sensor Abnormality (F37)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet
temperature sensor are used to determine sensor error.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.