Advertisement

In case of a power supply failure or pump operating failure, drain the system (as suggested in the figure below).
When water is idle inside the system, freezing up is very likely to happen which could damage the system.
Drainage piping installation
Use a drain hose with inner diameter of 15 mm.
The hose must be installed in a continuously downward direction and left open to the frost-free atmosphere.
If drain hose is long, use a metal support fixture along the way to eliminate the wavy pattern of drain tube.
The water may drip from this discharge hose. Therefore must guide the hose without close or block the outlet of
the hose.
Do not insert this hose into sewage hose or cleaning hose that may generate ammonia gas, sulfuric gas, etc.
If necessary, use a hose clamp to tighten the hose at drain hose connector to prevent it from leaking.

11.4 Connect The Cord And Cable To Mono Bloc Unit

(REFER TO WIRING DIAGRAM AT UNIT FOR DETAIL)
1
Cable connection to the power supply through isolating device (Disconnecting means).
Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
o
Connect the approved polychloroprene sheathed power supply 1 cord (5 x 1.5 mm
o
power supply 2 cord (3 x 1.5 mm
60245 IEC 57 or heavier cord to the RCCB, and to the other end of the cord to isolating
device (Disconnecting means).
2
To avoid cable and cord harmed by sharp edge, cable and cord must go through bushing (located at the right
side of Mono bloc unit) before carry out electrical connection. The bushing must be used and must not take off.
3
Secure the cable onto the control board with the holder (clamper).
How to guide power supply cords and optional
cable / cord for
MDC09C3E8
(View without internal wiring)
Illustration of how to fix drain hose to Monobloc Unit
2
) and power supply 3 cord (5 x 1.5 mm
How to guide power supply cords and optional
MDC12C9E8/MDC14C9E8/MDC16C9E8
(View without internal wiring)
42
2
2
), type designation
cable / cord for
) and