16.5.16 Compressor Rotation Failure (F14)
Malfunction Decision Conditions:
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused:
1
Compressor terminal disconnect.
2
Faulty outdoor unit PCB (main).
3
Faulty compressor.
Abnormality Judgment:
Continue 4 times in 20 minutes.