PowerRouter • Solar Inverter • Installation manual
G028-H
Hard
An error occurred on one of the
internal voltage supplies of the
grid module (G)
G029-S
Soft
The grid module (G) start-up
procedure failed
G031-H
Hard
There was an overpower on the
output of the PowerRouter
G034-H
Hard
See P092-H
G036-H
Hard
See P098-H
G039-S
Soft
The output power of the grid
module (G) has been reduced
because the grid frequency was
too high
G040-S
Soft
The output power of the grid
module (G) has been reduced
because the grid voltage was too
high
G041-S
Soft
The output power of the grid
module (G) has been reduced
because the 10 minute average of
the grid voltage was too high
G043-H
Hard
Error occured in anti-islanding
settings.
S002-S
Soft
The internal temperature of the
S023-S
solar module (S) is too high
The output power of the module
has been reduced
S004-S
Soft
The solar string voltage
connected to one or both of the
inputs exceeds 600 volts
S005-S
Soft
An overvoltage occurred on an
internal bus of the solar module
(S)
S007-S
Soft
An overcurrent occurred on an
internal circuit of the solar module
(S)
S013-S
Soft
The output power of the solar
panels exceeds 6000 watts
S016-S
Soft
There was an internal
communication error within the
PowerRouter
S019-H
Hard
See P092-H
S021-H
Hard
See P098-H
S024-S
Soft
Problem with the onboard supply
voltage, or the SOlar boost limiter
is activated.
Restart the system (section 7.6.1)
The system should recover from the error after the
restart
Contact your dealer if this error occurs frequently
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Turn off the loads connected to the PowerRouter
Restart the system (section 7.6.1)
The error will disappear and normal operation will
resume when the grid frequency is within approved
limits
The error will disappear and normal operation will
resume when the grid voltage is within approved
limits
The error will disappear and normal operation will
resume when the 10 minute average of the grid
voltage is within approved limits
Restart the system (section 7.6.1)
Run the installation wizard or tool again and select
country.
Check the airflow of the PowerRouter (section 7.6.2)
When the module cools down the error will
disappear and the normal operation will resume
Contact your dealer if this error occurs frequently
Check the solar panel configuration and wiring
The error will disappear when the voltage on both
strings drops below 600 volts
The error will disappear when the voltage drops
below the limit
Contact your dealer if this error occurs frequently
After ten minutes the error will disappear and
normal operation will resume
Contact your dealer if this error occurs frequently
This error will disappear when the power drops
below 6000 watts
Contact your dealer if this error occurs frequently
The error will disappear automatically and normal
operation will resume
Contact your dealer if this error occurs frequently
The system will recover automatically.
Contact your dealer if this error occurs frequently
7 Troubleshoot