7 Troubleshoot
P111-S
Soft
EN
P115-H
Hard
P118-H
Hard
G001-S
Soft
G037-S
G002-S
Soft
G003-S
Soft
G007-S
Soft
G011-S
Soft
G012-S
Soft
G013-H
Hard
G015-S
Soft
G023-H
Hard
G025-H
Hard
36
PowerRouter • Solar Inverter • Installation manual
The PowerRouter was not able to
configure the 3-phase sensor
The PowerRouter cannot function
correctly because some hardware
modules were not detected
The installation wizard failed.
The internal temperature of the
grid module (G) is too high
The output power of the module is
reduced
An overvoltage occurred on the
power backbone. The grid module
(G) will be temporarily turned off
An undervoltage occurred on the
power backbone. The grid module
(G) will be temporarily turned off
(e.g. the load on the local out is
higher than the power available in
the PowerRouter)
The voltage level on the local out
is too high in a situation where no
voltage is expected
An undervoltage occurred on the
local out. The local out will be
temporarily turned off.
An overvoltage occurred on the
local out. The local out will be
temporarily turned off (e.g. a very
high load connected to the local
out was suddenly disconnected)
A short circuit was detected on
the PowerRouter local out
There was an internal
communication error within the
PowerRouter
The local out output was
overloaded
See P027-H
Make sure the 3-phase sensor is connected
properly
Make sure the 3-phase sensor is not in the locked
position
Restart the system (section 7.6.1)
Contact your dealer if this error occurs
Restart the system (section 7.6.1)
Run the installation tool or install wizard again
Contact your dealer if this error occurs frequently
Check the PowerRouter airflow (section 7.6.2)
Once the module cools down the error will
disappear and normal operation will resume
Contact your dealer if this error occurs frequently
Once the voltage drops below the safe level the
error will disappear and normal operation will
resume
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
If this error occurs during installation make sure the
grid is connected to the "AC GRID" connection
When this error occurs during normal operation an
error has occurred in connection with the anti-
islanding safety requirements
Restart the system (section 7.6.1)
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
Check the wiring connected to the local out for a
short
Restart the system (section 7.6.1)
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Turn off the loads connected to the PowerRouter
Restart the system (section 7.6.1)