Dc Wiring / Dc Earthing; Specifications - Latronics PVE1200 Instruction Manual

Latronics pv edge grid connected inverter with energy meter
Hide thumbs Also See for PVE1200:
Table of Contents

Advertisement

SPECIFICATIONS

Model
Input Data
Maximum Solar Input Power
Maximum DC Input Current
Maximum DC Input Voltage
Maximum Power Point
54VDC - 100VDC
Tracking Range
Ideal Operating Window
(Array VOC)
Automatic Turn ON (PV
Mode)
Automatic Turn ON (Battery
mode)
Starting Operation
Reverse Polarity Protection
Short Circuit Diode Across DC Input Terminals
Output Data
Output Power
1100W at 50ºC (1250W Max) 2100W at 50ºC (2500W Max)
Output Voltage Range
Output Frequency
Peak Efficiency
Night Time Power
NIL. Automatically Disconnects from AC Grid
Consumption
Input/Output Isolation
Operating Temperature
Anti islanding Protection
Over/under voltage, Over/under frequency, Active phase shift
General Data
Status Indicators
LCD Meter - Power, Voltage, Current, Power Factor,
Wall Mount Enclosure
330mm
Dimensions
Weight
Connections
Warranty
PVE1200
PVE2500
1600W
3100W
25A
25A
103V
206V
108VDC - 200VDC
75-92VDC
150-185VDC
70VDC
140VDC
54VDC
108VDC
10W
205 - 265 Vac
50Hz tolerance +/- 1Hz
94%
95%
3500V via Toroidal Transformer
-10ºC to 50ºC
Output power in 25% Increments
Grid Monitoring - Stability check
Solar Input ON
Grid Fault
Overload
Powder Coated Aluminum
x 296mm
x
370mm
x 386mm
H
W
H
150mm
180mm
D
11 kg
22 kg
AC/DC Pluggable Connectors
5 years
18
Check solar array will not exceed inverter's maximum voltage rating
* The inverter is designed to operate with a 48V nominal solar panel array
(PVE1200) or 96V nominal solar panel array (PVE2500).
* A 48V nominal solar array at a temperature of 25
circuit voltage less than 92V
* A 96V nominal solar array at a temperature of 25
circuit voltage less than 185V
*
If other sources of DC input are required e.g. wind turbines, micro hydro
turbines etc. A battery bank or Latronics Turbine Controller (see pg 9) will
be required with the Maximum Power Point Tracking (MPPT) disabled
(see pg 13).
*
The DC input voltage is stated on the PV Edge compliance label and the
technical specifications sheet within this manual. Check that the input
voltage is within the required limits and does not exceed the maximum
limit (see pg 18).
*
Recommended cable size for the DC Input is 6sqmm with an insulation
rating of 0.6/1KV.
*
A DC isolator is required to be installed next to the inverter to isolate the
inverter for maintenance.
*
Observe Polarity.
*
Ensure the DC Isolators are off when connecting the DC Leads
The PV Edge inverter is suitable for use with solar arrays that require positive
x
or negative earthing. Due to the inverter's galvanic isolation between AC and
W
D
DC inputs no additional modifications are required. Simply connect the
positive or negative of the solar array to the system earth.
DC WIRING
of 103V (PVE1200) or 206V (PVE2500)
POSITIVE/NEGATIVE EARTHING
3
°C
should have an open
°C
should have an open