8
DIP SWITCH SETTINGS
Switch 1 -MPPT / Battery mode
In the ON position
(default)
the Maximum Power Point Tracking is enabled.
This is required when the DC input is Photovoltaic Solar Modules only.
In the OFF position the Maximum Power Point Tracking is disabled and the
voltage tracking will operate at a fixed voltage of 54V (PVE1200) or 108V
(PVE2500). This setting is required in a system where a 48V (PVE1200) or
96V (PVE2500) Battery Bank is required on the DC input.
Switch 2 - 50/60 Hz
In the ON position the Inverter is set for 60Hz operation.
In the OFF position
(default)
the Inverter is set for 50Hz operation.
Switch 3
(If Switch 1 OFF)
ON = Gel/SLA battery.
OFF = Flooded battery.
(Default)
Switch 4
Must be in OFF position
(default)
factory AC test setting.
Switch 5
Must be in the OFF position
(default)
is a factory DC test setting.
Switch 6
Not used.
ON
1 2 3 4 5 6
OFF
WARNING:
Due to dangerous voltages existing inside the unit, make sure
the external DC and AC solar isolators are turned off before
opening the unit. Only
qualified Trades Persons
adjust these settings.
(If Switch 1 ON)
ON = 255VAC sustained operation
OFF= Sustained operation turned off
for normal operation. The ON position is a
for normal operation. The ON position
DIP SWITCH LOCATION
MAIN PCB
DIP Switch located on Main PCB
are permitted to
13