Dip Switch Settings - Latronics PV Edge Grid Connect Instruction Manual

Grid interactive solar system inverter
Table of Contents

Advertisement

8

DIP SWITCH SETTINGS

Switch 1 -MPPT / Battery mode
In the ON position
(default)
the Maximum Power Point Tracking is enabled.
This is required when the DC input is Photovoltaic Solar Modules only.
In the OFF position the Maximum Power Point Tracking is disabled and the
voltage tracking will operate at a fixed voltage of 54V (PVE1200) or 108V
(PVE2500). This setting is required in a system where a 48V (PVE1200) or
96V (PVE2500) Battery Bank is required on the DC input.
Switch 2 - 50/60 Hz
In the ON position the Inverter is set for 60Hz operation.
In the OFF position
(default)
the Inverter is set for 50Hz operation.
Switch 3
Battery type selector not used if switch 1 is ON.
ON = Gel/SLA battery.
OFF = Flooded battery.
(default)
Switch 4
Must be in OFF position
(default)
a factory AC test setting.
Switch 5
Must be in the OFF position
(default)
is a factory DC test setting.
Switch 6
Not used.
ON
1 2 3 4 5 6
OFF
WARNING:
Due to dangerous voltages existing inside the unit, make sure
the DC circuit breaker and AC solar isolator are turned off
before opening the unit. Only
permitted to adjust these settings.
for normal operation. The ON position is
for normal operation. The ON position
DIP SWITCH LOCATION
MAIN PCB
DIP Switch located on Main PCB
qualified Trades Persons
13
are