Basic Programming
Now let's look at how to change some
of the default settings listed on the
previous page. If you are using the
Classic PC1565 as a "bells only"
system, this could be the only pro-
gramming you need to do.
For example, let's look at changing
the entry delay from default 30 sec-
onds to 45 seconds. Entry delay is in
section 005, "System Times", on
page 29 of the Installation Manual.
All entries in section 005 require 3
digits.
To get into engineering programming
mode you must press [*][8] followed
by your engineering code. At default
this will be [5555]. At this point the
keypad will display "Enter Section"
followed by three dashes. Enter the
three-digit number of the section you
want to program, in this case [005].
You will see the digits 030 displayed
indicating the default time of 30
seconds. Enter [045] for the new entry
delay time. If this is the only change
you want in section 005, you can now
press [#] to exit this section and save
the change. If you want to make
another change, ("Exit Delay", for
example), then use the arrow keys
until 120 is displayed (the default
setting).