4219/4229 Expansion Zones - Honeywell ADEMCO VISTA-48A Installation And Setup Manual

Hide thumbs Also See for ADEMCO VISTA-48A:
Table of Contents

Advertisement

+
5
RELAY
PROGRAM
AUX PWR
RELAY
OUTPUT
AS ZONE
TYPE 54
TERMINALS
(FIRE ZONE
RESET)
_
4
N.C.
CONTACT OPENS
MOMENTARILY UPON
+
_
FIRE ALARM RESET
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
+
TO ZONE TERM. ( )
HEAT
DETECTOR
_
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Relay for Power Reset

4219/4229 Expansion Zones

1. Connect each module to the control's keypad terminals.
If power supervision is required, use the Trigger
Module terminals as described in the Aux Power
Supervision Connections paragraph in the Wiring
to Keypads section (page 2-3).
2. Assign each module a unique device address (07-11)
using its DIP switches. Device addresses determine
the zone numbers being used, as shown in the
following table.
Expander Module Addresses
For Zones...
09-16
17-24
25-32
33-40
41-48
3. Connect sensors to the module's loops.
4. If using relays with the 4229, connect the desired
field wiring to the unit's relay contact terminals.
RELAY
CONNECTOR
RLY
RLY
2
1
RELAYS OFF
Figure 7. 4-Wire Smoke Detector Connections
_
BLK
+
RED
EOL
POWER
N.O.
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
VIOLET
WHEN POWER
IS APPLIED.
2000
OHMS
EOLR
Set Module to Device Address...
07
(not available if zone-doubling enabled)
08
09
10
11
RELAY
DIP SWITCH
2
FOR SETTING ADDRESS
AND ZONE "A" RESPONSE
RELAY
1
NO C NC
TAMPER JUMPER POSITION
4229 IN CABINET
(NOT TAMPER)
4229 REMOTE
(TAMPER PROTECTED)
1
2
3
4
REED
(TAMPER)
SWITCH
C
ZONES
A
B
Figure 8. Wiring Connections, 4219 & 4229 (4229 shown)
+
( )
5
AUX PWR
_
( )
TO OUTPUT 17
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN
79 MENU
MODE AND AS ZONE
TYPE 54 IN
4-WIRE SMOKE
OR COMBUSTION
80 MENU MODE
TO ZONE TERM. ( )
+
HEAT
DETECTOR
_
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Output 17 for Power Reset
Notes
• Supports up to 40 expansion zones (NO or NC)
using 4219/4229 Zone Expander Modules as
follows:
• Use 1000 ohm end-of-line resistors at the end of
loops connected to the 4219/4229 modules. (End-
of line resistors used on the control terminals are
2000 ohms.)
• Expansion zones have normal response time
(400–500 msec), except zone connected to each
module's loop "A," which can be set for fast
response (10–15 msec).
4229
EITHER OR BOTH CAN BE USED
4-PIN CONSOLE PLUG
TB1
5
6
7
8
9
12
10
11
D
E
F
G
H
Mounting and Wiring the Control
_
BLK
+
RED
EOL
POWER
SUPERVISION
N.O.
+
_
RELAY MODULE
VIOLET
A77-716B.
USE N.O.
DETECTOR
2000
CONTACT,
OHMS
WHICH CLOSES
EOLR
WHEN POWER
IS APPLIED.
TERMINALS ON
CONTROL PANEL
TB2
GRN
DATA OUT (>)
(TERM 6)
4
TO CONTROL
BLK
(–) GROUND
3
(TERM 4)
4
3
RED
(+) 12VDC
2
(TERM 5)
2
DATA IN (<)
YEL
1
FROM
(TERM 7)
1
CONTROL
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE
300 OHMS + EOL)
4229-002-V0
2-7