78 FLAME LOss
If the boiler is Reset, does the boiler Ignite for a
Is the Gas Pressure available at the boiler > 18 mbar?
Is 215Vdc available at the Gas Valve during
Check Spark Generator and associated Harness
for continuity, visual condition and position (refer to
Frame 65). Are these functioning correctly?
Check Ignition Electrode and associated Harness
for continuity, visual condition and position (refer to
Frame 58). Are these functioning correctly?
Check Syphon and condensate drain pipework
for blockage and rectify if necessary. Boiler now
* Note: due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to measure
the value. In general terms a reading of greater than 150V indicates that the correct voltage is supplied to the gas
valve
79 ThERMAL FUsE LOCKOUT
Isolate the electrical supply to the boiler and system
Ensure that the electrical connection to the thermal
fuse is pushed fully home and that the 6 way connector
is properly connected to the primary PCB.
Disconnect the 6 way connector to the thermal fuse.
Is there continuity across the black and yellow wires
Disconnect the electrical connection to the thermal
fuse. Is there continuity across the fuse?
60
Fault Finding
short time and then Extinguish
No
Yes
ignition? (* See note)
Yes
Yes
Yes
working OK?
Press r, is the fault still present?
Yes
in pins 1 and 2?
No
No
Replace the heat exchanger
Yes
Check the Detection Electrode and associated Harness for
continuity, visual condition and position (refer to Frame 64).
Check if the Condensate Pipe is blocked. Check if the Flue
is blocked. Replace as necessary
No
Check Gas Supply and rectify fault
No
Check wiring from Gas Valve to PCB and replace if
necessary, otherwise replace the main PCB
No
Replace Spark Generator and Harness
as necessary
No
Replace Ignition Electrode and
associated Harness as necessary
No
Replace Gas Valve
Yes
Replace the primary PCB
Yes
Replace the wiring from the PCB to the
thermal fuse