ENSURE THAT THE POWER CORD TO THE MACHINE HAS
BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE
MAINTENACE ON ITEMS 1, 2, 3, 4, AND 5.
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
1. Clean the surface of the evaporator and condenser coils by blowing
the dirt out from behind the fins with compressed air. Hold the nozzle
of the air hose away from the coil (approx 6") to avoid damaging the
fins. Alternatively, vacuum clean the coils.
DO NOT STEAM CLEAN REFRIGERATION COILS
2.
Check that the fan is firmly secured to the motor shaft and that the
fan rotates freely. The fan motor is sealed for life and therefore
does not need oiling.
3.
To check the refrigerant charge, run the unit for 15 minutes and
briefly remove the cover. The evaporator coil should be evenly frost
coated across its surface. At temperatures above 25°C, the coil
may be covered with droplets of water rather than frost. Partial
frosting accompanied by frosting of the thin capillary tubes,
indicates loss of refrigerant gas or low charge.
4.
Check all wiring connections.
5.
To check the operation of the defrost system, ensure the air
temperature is below 20 ºC, switch the machine on and leave it
running for approximately 1 hour. The machine will then enter "Hot
Gas" defrost mode for approximately 5 minutes before returning to
normal operation. If the unit will not defrost, the printed circuit timer
board/sensor may be defective or the by-pass valve may be
inoperable.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
S
C
ERVICE
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

ROUTINE MAINTENANCE

WARNING:
WARNING:
PREVENT PERMANENT DAMAGE
Page 8 of 16