Routine Maintenance - EIP TRITON Owner's Manual

Triton industrial dehumidifier
Table of Contents

Advertisement

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN
DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTNENANCE
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
1.
Replace or clean the inlet air grille as required. Clean the surface
of the evaporator and condenser coils by blowing the dirt out from
behind the fins with compressed air. Hold the nozzle of the air hose
away from the coil to avoid damaging the fins.
vacuum clean the coils.
DO NOT STEAM CLEAN REFRIGERATION COILS
2.
Check that the fan is firmly secured to the motor shaft and that the
fan rotates freely. The fan motor is sealed for life and therefore
does not need oiling.
3.
To check the refrigerant charge, run the unit for 15 minutes and
briefly remove the top cover. The evaporator coil should be evenly
frost coated across its surface. At temperatures above 70°F, the
coil may be covered with droplets of water rather than frost. Partial
frosting accompanied by frosting of the thin capillary tubes,
indicates loss of refrigerant gas or low charge.
4.
Check all wiring connections.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
S
C
ERVICE
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

ROUTINE MAINTENANCE

WARNING:
WARNING:
PREVENT PERMANENT DAMAGE
Page 6 of 16