SECTION 4
OPERATION
4.3

ROUTINE POWER-UP

After it has been verified that the installation is correct, follow the steps below for routine operation.
LETHAL VOLTAGES ARE PRESENT AT THE INPUT AND OUTPUT TERMINALS OF THIS EQUIPMENT!
DES TENSIONS A CARACTERE MORTEL SONT PRESENTES SUR LES BORNES D'ENTRÉE ET DE
1. Set the OUTPUT POWER switch to the OFF position.
2. Switch the INPUT POWER switch to the ON position. The controller will light up and begin to
display output data.
DO NOT CONNECT ANY LOADS TO THE OUTPUT OF THE POWER SOURCE UNTIL THE OUTPUT
VOLTAGE AND FREQUENCY HAVE BEEN VERIFIED AS CORRECT.
APPLICATION OF IMPROPER VOLTAGE OR FREQUENCY CAN DAMAGE LOADS.
NE RACCORDER AUCUNE CHARGE SUR LA SORTIE DE L'EQUIPEMENT SANS AVOIR AU PREALABLE
VERIFIE ET VALIDE LES PARAMETRES DE SORTIE TENSION ET FREQUENCE
L'APPLICATION DE TENSION ET FREQUENCE INCORRECTES PEUT ENDOMMAGER LES CHARGES
3. Set the OUTPUT POWER switch to the ON/AUTO position and press the UPC OUTPUT
ENABLE switch to set it to the ON position.
4.4

SYSTEM TURN-OFF

The ACX Power Source is turned off by:
1. Set the OUTPUT POWER Switch to the OFF position.
2. Open the INPUT POWER circuit breaker.
WARNING
ATTENTION
SORTIE DE CET EQUIPEMENT!
CAUTION
PRECAUTION
CONNECTEES A L'EQUIPEMENT
30