Takagi T-KJr2-IN Installation Manual And Owner's Manual page 26

On-demand
Table of Contents

Advertisement

A remote controller is not required for the Easy-Link system.
NOTICE
If running the Easy-Link system without a remote controller, please make sure the
temperature settings on ALL the units are set to the same settings. Otherwise, the
units will not operate properly.
If a remote controller is used, the temperature on all the units in the system will
automatically be set to the same temperature that is set on the remote.
(C) Examples of incorrect settings and/or connections
CASE 1:
Unless you change dipswitch No.1 of the "PARENT" unit to the "ON" position, the
system will not work as an Easy-Link system. The units will operate as individual units.
Prohibited
CASE 2:
If you connect the
connector of the "CHILD-1" unit, the system will not work as an Easy-link system. The units will
operate as individual units.
Prohibited
PARENT unit
Co n n e c t or s
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
Communication cable
Wrong dipswitch
setting on the
"PARENT" unit
Wrong Setting
"
"
[1] (or [2])
connector of the "PARENT" unit to the
Wrong connections between the "PARENT" unit and the "CHILD-1" unit
CHILD-1 unit
C o nn e c t o rs
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
Wrong
Connections
PARENT unit
C o n n e c t o r s
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
Communication cable
PARENT unit
C o n n e c t o r s
OR
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
Communication cable
26
Page
Installation
CHILD-1 unit
C o n n e c t o r s
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
"
PARENT (or [1])
CHILD-1 unit
C o n n e c t o r s
Right bank of Dipswitches
1 2 3 4 5 6
ON
OFF
Wrong
Connections
"

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents