Maximum Delivery Capacity of Cubic Feet of Gas per Hour of IPS Pipe Carrying Natural Gas of 0.60 Specific Gravity
Based on Pressure Drop of 0.5" WC
Based on Energy Content of 1,000 BTU/Cubic Ft.: The water heater requires 140 Cubic Ft./hr for the 110 (T-KJr2)
models, 190 Cubic Ft./hr for the 310 (T-K4) models, and 199 Cubic Ft./hr for the 510 (T-D2) models.
Pipe Size
Diameter
10'
¾"
363
1"
684
1 ¼"
1,404
1 ½"
2,103 1,445 1,161
2"
4,050 2,784 2,235 1,913 1,696 1,536 1,413 1,315 1,234 1,165 1,033
Maximum Capacity of Propane (LP) Based on 11" WC supply pressure at a 0.5" WC pressure drop
Pipe Size
Diameter
10'
¾"
567
393
1"
1,071
732
1 ¼"
2,205 1,496 1,212 1,039
1 ½"
3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023
2"
6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
For more information, please see the below.
Gas Sizing Example
Water
Heater
199,000BTU
10' Length
5' Length
3/4" Pipe Size
1-1/4" Pipe Size
A
10' Length
5' Length
1" Pipe Size
1-1/4" Pipe Size
Gas Meter
-Natural Gas Supply Piping-
20'
30'
40'
249
200
171
470
377
323
965
775
663
993
-Propane (LP) Supply Piping-
20'
30'
40'
315
267
590
504
(Natural Gas)
Dryer
35,000BTU
15' Length
B
1" Pipe Size
10' Length
3/4" Pipe Size
C
Range
Furnace
65,000BTU
120,000BTU
Length
50'
60'
70'
152
138
127
286
259
239
588
532
490
880
798
734
Length
50'
60'
70'
237
217
196
448
409
378
913
834
771
Based on Energy Content of 1,000BTU/Cubic Ft:
Divide each appliance's BTU requirement by 1,000BTU to get
the appliances Cubic Ft. requirement.
Take into account the distance the appliance is from the gas
meter, look in the above gas chart to properly size the line.
For sections of the gas line supplying gas to more than one
appliance (Ex: Point A to Point B), add up the cubic ft.
10' Length
requirements of the appliances that are being supplied by that
1/2" Pipe Size
section, and size to the farthest appliance.
For Example: The section from A to B supplies gas to the
15' Length
furnace, range, and dryer. Adding up the BTU requirements
and dividing by 1,000 yields a cubic ft. requirement of 220
1/2" Pipe Size
cubic ft. of gas. The farthest appliance is the range, which is 50
ft. away from the meter. Looking at the above chart, and
under the column of 50ft., Section A to B needs to be 1" in
order to supply 220 cubic ft.
18
Page
Installation
Unit: Cubic Feet per Hour
80'
90'
100'
118
111
104
222
208
197
456
428
404
683
641
605
80'
90'
100'
125'
185
173
162
346
322
307
724
677
630
976
125'
150' 200'
93
84
72
174
158
135
358
324
278
536
486
416
936
801
Unit: kBTU per Hour
150'
200'
146
132
112
275
252
213
567
511
440
866
787
675
1,260

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents