Troubleshooting; Guide To Status Indicators - Liebert PSP User Manual

Power availability 350-650 va 120v
Table of Contents

Advertisement

T
ROUBLESHOOTING
The information below indicates various symptoms a user may
encounter in the event the PowerSure PSP experiences a problem. Use
this information to determine whether external factors caused the
problem. See Troubleshooting Chart for suggested remedy.
Utility
Indicator
Fault
Battery
Indicator
Indicator

Guide to Status Indicators

Fault
Indicator
Green
Flashing
Green
Flashing
Green
ON
Green
ON
Green
ON
Red
Flashing
Red
ON
1. The Fault indicator illuminates, indicating the
UPS detected a problem.
2. An alarm sounds, alerting that the UPS
requires attention. The alarm can be silenced
except for low battery, overload and
over-temperature warning conditions.
3. Utility and/or Battery indicators may be
illuminated as a diagnostic aid to the operator,
as shown below:
Utility
Indicator
Green
ON
Green
ON
Green
ON
Green
ON
Green
ON
Battery
Indicator
Normal operation with utility
power present; no beep.
Green
UPS is operating on battery;
ON
beep every 10 seconds.
Green
Battery test has been
ON
initiated; no beep.
Amber
Battery needs to be replaced;
Flashing
long beep every minute.
Amber
Low battery warning; beep
Flashing
every half-second.
Overload warning, load is
>100%; beep every half-
second.
Overload shutdown, load
exceeds UPS capacity
(110%); continuous beep.
Over temperature (overtemp)
warning; beep every
5 seconds (Normal mode).
Over temperature (overtemp)
Green
warning; beep every
ON
5 seconds (Battery mode).
Over temperature (overtemp)
shutdown; long beep every
5 seconds.
UPS is on, fault warning;
continuous beep.
UPS has failed & shut down;
continuous beep.
20
Diagnosis/
Audible Alarm