The information below indicates various symptoms a user may encounter in the
event the UPStation GXT™ develops a problem.
determine whether external factors cause the problem and how to remedy the
situation.
1.
The fault indicator will illuminate indicating the UPS detected a problem.
2.
An alarm will sound, alerting that the UPS requires attention.
3.
One or more additional load/battery level LED indicators will be illuminated
to provide a diagnostic aid to the operator, as described below:
All.
On bypass due to output overload (beep every half second)
A.
On bypass due to over temperature condition (beep every 4 seconds)
B.
On bypass due to DC bus overvoltage (beep every 4 seconds)
C.
On bypass due to control power supply failure (beep every 4 seconds)
D.
On bypass due to PFC failure (beep every 4 seconds)
E.
On bypass due to inverter failure (beep every 4 seconds)
A&C.
UPS failed battery test (long beep every minute)
C&E.
UPS shutdown due to command from communication port (SNMP); no beep
The fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while battery charger is not
operational.
If a problem persists consult your dealer, or contact Liebert
Technical Support (LTS). World Wide Technical Support numbers are located at
the end of this section.