Table of Contents

Advertisement

Harrie Leenders Doran ­ Instructions for Installation, Use and Maintenance 
PREPARATORY WORK AND SAFETY CHECKS 
IMPORTANT WARNING 
This stove must not be installed into a chimney that serves any other heating appliance. 
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit 
fumes into the room. 
Chimney 
In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate 
draught of approximately 15 Pa so as to clear the products of combustion and prevent smoke problems into 
the room. 
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the 
top of the chimney should be satisfactory. Alternatively the calculation procedure given in EN 13384­1 may 
be used as the basis for deciding whether a particular chimney design will provide sufficient draught. 
The outlet from the chimney should be above the roof of the building in accordance with the provisions of 
Building Regulations Approved Document J. 
If installation is into an existing chimney then it must be sound and have no cracks or other faults which 
might allow fumes into the house. Older properties, especially, may have chimney faults or the cross sec­ 
tion may be too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if required, seek­ 
ing expert advice, if necessary. If it is found necessary to line the chimney then a flue liner suitable for solid 
fuel must be used in accordance with Building Regulations Approved Document J. 
Any existing chimney must be clear of obstruction and have been swept clean immediately before installa­ 
tion of the stove. If the stove is fitted in place of an open fire then the chimney should be swept one month 
after installation to clear any soot falls which may have occurred due to the difference in combustion be­ 
tween the stove and the open fire. 
If there is no existing chimney then any new system must be to the designation described above and in ac­ 
cordance with Building Regulations Approved Document J. 
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for use as 
the complete chimney. The chimney and connecting fluepipe must have a minimum diameter of 150 mm 
and its dimension should be not less than the size of the outlet socket of the stove. 
Any bend in the chimney or connecting fluepipe should not exceed 45°.  90° bends should not be used. 
Combustible material should not be located where the heat dissipating through the walls of fireplaces or 
flues could ignite it. Therefore when installing the stove in the presence of combustible materials due ac­ 
count must be taken of the guidance on the separation of combustible material given in Building Regula­ 
tions Approved Document J and also in these stove instructions. 
If it is found that there is excessive draught in the chimney then a draught stabiliser should be fitted. Fitting 
of a draught stabiliser will affect the requirement for the permanent air supply into the room in which the 
stove is fitted in accordance with Approved Document J (see also combustion air supply). 
Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney 
and connecting fluepipe where it is not intended for the chimney to be swept through the appliance.

Advertisement

Table of Contents
loading

Table of Contents