Fuel Specifications - Kohler KG2204 Operation

Hide thumbs Also See for KG2204:
Table of Contents

Advertisement

Fuel Specifications

NOTICE
Natural gas and propane installations must be
installed in accordance with applicable federal,
state, and local law, and with the National Fire
Protection Association (NFPA) Pamphlet #58,
standard for storage and handling of Liquefied
Petroleum Gases, to the extent that these
standards are not in violation of federal, state, or
local law.
Fuel Type
Liquid Propane
Type
Gas (LPG)
Maximum fuel pressure
(engine OFF, no load)
Minimum fuel pressure
(engine ON, full load)
Natural Gas (NG)
Supply
Approximate supply volume
Minimum flow
Allowable water vapor
Maximum fuel pressure
(engine OFF, no load)
Minimum fuel pressure
(engine ON, full load)
LPG and NG
Fuel handling and supply component
(both)
constraints
Operating temperature range
TP-6901 6/14
Table 4-1: Fuel Specifications
Item
Specification
HD-5 or HD-10
13.85" W.C.
6.0" W.C.
Standard pipeline
3
37.257 kJ/m
(1000 BTU/ft.
3
11.9 m
/hr. (420 SCFH) @ 6.0" W.C.
Less than 112.3 kg per 1 million m
(Less than 7 lb. per 1 million ft.
13.85" W.C.
6.0" W.C.
UL 2200: Standard for Stationary Engine
Equipment Assemblies
–20°C (–4°F) to 105°C (221°F)
OPERATION
3
)
3
3
)
Operation 17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents