Recommended Mounting Heights And Coverages - Brant Radiant Heaters DX2-20-60 User Manual

Gas-fired infrared tube heater
Table of Contents

Advertisement

DX2
Series
Chart 3.1 •

Recommended Mounting Heights and Coverages

Note: This chart is provided as a guideline. Actual conditions may dictate variation from this data.
20 ft.
50-65 MBH
75-100 MBH
30 ft.
50-65 MBH
75-125 MBH
40 ft.
50-65 MBH
75-125 MBH
150-175 MBH
50 ft.
100-125 MBH
150-200 MBH
60 ft.
125 MBH
150-200 MBH
70 ft.
175-200 MBH
80 ft.
200 MBH
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too low
or too high, they may result in discomfort or lack of heat. Detroit Radiant Products Company generally
recommends observing the recommended mounting heights to optimize comfort conditions. However,
certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings
may result in the heaters being mounted outside of the factory recommended mounting heights.
Figure 3.3
Mounting Height Dimensions (see Chart 3.1 for dimensions)
Dimension B
Distance between
heater rows
Dimension C
Maximum distance between heater and wall
Note: Dimensions A, B & C are based upon heaters hung at the factory recommended mounting height.
3.0
Installation
10' - 16'
20' x 12'
12' - 20'
22' x 15'
10' - 16'
30' x 14'
12' - 20'
33' x 18'
10' - 16'
40' x 16'
12' - 20'
44' x 21'
16' - 30'
45' x 26'
15' - 25'
55' x 24'
16' - 30'
56' x 30'
16' - 25'
66' x 27'
17' - 40'
67' x 34'
17' - 40'
78' x 38'
18' - 45'
89' x 42'
Dimension A
Dimension A
Recommended Mounting Heights and Coverages
12' x 12'
10' - 20'
N/A
20' - 30'
17' x 13'
10' - 20'
18' x 15'
20' - 30'
22' x 14'
10' - 20'
23' x 17'
20' - 30'
24' x 20'
30' - 40'
28' x 19'
20' - 30'
29' x 23'
30' - 40'
33' x 21'
20' - 30'
34' x 26'
30' - 40'
39' x 29'
30' - 40'
44' x 32'
30' - 40'
13
20' - 40'
16'
30' - 50'
18'
20' - 40'
17'
30' - 50'
20'
20' - 40'
20'
30' - 50'
20'
40' - 60'
25'
30' - 50'
25'
40' - 60'
25'
30' - 50'
25'
40' - 60'
25'
40' - 60'
30'
40' - 60'
30'
Dimension C
Maximum
distance
between
heater
and wall

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents