Sidewall (Horizontal) Venting - Brant Radiant Heaters DX2-20-60 User Manual

Gas-fired infrared tube heater
Table of Contents

Advertisement

DX2
Series
Figure 3.21
General Vent Requirements
Adjustable Roof Flashing
1 in. Minimum Clearance
1 in. Minimum Clearance
Single-Wall Elbow or Alternate Tee Fitting
Sidewall Venting
Guidelines:
Vent Pipe Angle
• To prevent moisture from entering the heater system, slope the vent pipe down toward the outlet
1/4 in. per foot of length. Do not pitch the heater.
• **Vent must extend beyond any combustible overhang if the vent is less than 36 in. below the
combustible overhang.
Figure 3.22
Sidewall Venting Requirements
Building Overhang
Sidewall Vent Cap
Wall Thimble
Vent Cap
Storm Collar
B to C Adapter
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12
36 in.
min.**
6 in.
min.**
3.0
Installation
24 in.
Min.*
Sidewall
B to C Adapter
Double-Wall
Single
B-Vent
Wall Vent
1/4 in. downward
pitch per foot
27
Venting
Sidewall Venting
Roof*
Double-Wall B Vent
Firestop Spacer
Heater
Single-wall Vent (field supplied)
Heater