Rack Position - Toshiba IP edge EP Installation Manual

Hide thumbs Also See for IP edge EP:
Table of Contents

Advertisement

EP SERVER CHASSIS INSTALLATION

Rack Position

15.9
1U
15.9
12.7
15.9
1U
15.9
12.7
15.9
1U
15.9
12.7
15.9
1U
15.9
EIA Standard Equipment Rack
hole spacing is shown.
Figure 2-17 IPedge Equipment Rack Position
Installation Manual
August, 2011
The EP server requires 2U vertical space in the equipment rack. The
server is 1.35 U high. The extra space must be left above the EP server
chassis. Refer to
Figure
Leave this area empty.
9.5
6
2-5.
Other Equipment
29
IPedge
60
EP Server
0.7
Other Equipment
All measurements are in mm
Rack Position
2-17