11.6 Powerful Mode Operation

When the powerful mode is selected, the internal setting temperature will shift lower up to 2°C (for Cooling/Soft
Dry) than remote control setting temperature for 20 minutes to achieve the setting temperature quickly.
Powerful operation stops condition
When one of the following condition is satisfied, powerful operation stops:
o
Quiet button is pressed.
Stop by OFF/ON button.
OFF Timer activates.
Powerful button is pressed again.
Powerful operation continue for 20 minutes.

11.7 Economy Mode Operation

This operation is use to reduce electrical power consumption by adjusting the set temperature.
Economy operation starts when the Economy button is pressed during cooling or dry operation.
During Cooling/Dry economy operation, target setting temperature will be adjusted by +2°C. Internal setting
temperature limit shift to maximum 35°C (maximum 33°C + 2°C Economy shift).
During Economy operation, all indicators includes Economy indicator will be dimmed. The brightness level is
equivalent to indicator dim function.
Powerful, Quiet and Economy could not be operated at the same time. The unit will follow the latest setting of
these three operations.
The Economy operation stops when:
1
Operation OFF.
2
Received Economy signal from remote control again.
3
Received either Powerful or Quiet operation signal from remote control.

11.8 Timer Control

There are 2 sets of ON and OFF timer is available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.
11.8.1 ON Timer Control
ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than
the setting time. This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
11.8.2 OFF Timer Control
OFF Timer 1 and OFF Timer 2 can be set using remote control, the unit with timer set will stop at set time.

11.9 Auto Restart Control

When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.