Panasonic WH-MXF09D3E5 Service Manual page 91

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MXF09D3E5:
Table of Contents

Advertisement

16.5.23. Four Way Valve Abnormality (F25)
Malfunction Decision Conditions:
1. During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C.
2. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C.
Malfunction Caused:
1. Faulty sensor.
2. Faulty connector connection.
3. Faulty outdoor unit PCB (noise filter/main).
4. Faulty four way valve.
Abnormality Judgment:
Continue 4 times in 30 minutes.
91