Panasonic WH-MXF09D3E5 Service Manual page 42

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MXF09D3E5:
Table of Contents

Advertisement

5. Route the remote controller cable (2) inside the lower
case in accordance with the intended feeding-out
direction. (Refer to the illustration at below)
6. Insert firmly the connector of remote controller cable (2)
to connector (CON1) in the upper case circuit board.
(Refer to the illustration at below)
7. Secure the remote controller upper case to the lower
case with the tabs provided.
11.4.3.3. Connecting The Remote Controller's Cable To Mono bloc Unit
Be sure to turn off the main power before installing and connecting the
remote controller. Otherwise, it will cause the electrical shock.
1. Remove the cabinet front plate.
2. Connect the remote controller's cable with the provided
connector as shown in below illustration. (Refer wiring
diagram for detail.)
3. Guide the remote controller cable through the clamper
and Bushing
.
(Refer illustration "How to connect Remote Controller to
Provided Connector" for detail.)
4. Reinstall the cabinet front plate after connection
complete.
11.4.3.4. Disposal of Mono bloc Unit Drain Water
• When a Drain elbow
- The unit should be placed on a stand which is taller than 50mm.
- Cover the 8 holes (ø20mm) with Rubber cap
• If the unit is used in an area where temperature falls below 0°C for 2 or 3 consecutive days, it is recommended not to use the
Drain elbow
and Rubber cap
is used, please ensure to follow below:
, for the drain water freezes and the fan will not rotate.
(refer to illustration below)
42