Panasonic WH-MXF09D3E5 Service Manual page 88

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MXF09D3E5:
Table of Contents

Advertisement

16.5.20. IPM Overheating (F22)
Malfunction Decision Conditions:
During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor.
Malfunction Caused:
1. Faulty outdoor unit fan motor.
2. Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 30 minutes.
88

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxf12d6e5

Table of Contents