Panasonic WH-MXF09D3E5 Service Manual page 81

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MXF09D3E5:
Table of Contents

Advertisement

16.5.13. Outdoor High Pressure Protection (H98)
Malfunction Decision Conditions:
During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor.
Malfunction Caused:
1. Faulty water pump.
2. Insufficient water flow rate in system.
3. Water leak in system.
4. 2/3 way closed.
5. Clogged expansion valve or strainer.
6. Excessive refrigerant.
7. Faulty outdoor high pressure sensor.
8. Faulty outdoor unit PCB (main).
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxf12d6e5

Table of Contents