Panasonic WH-MXF09D3E5 Service Manual page 48

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MXF09D3E5:
Table of Contents

Advertisement

12.1.5. Setting Water Outlet Temperature For Heat Mode
• The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the
internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor
temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water
temperature by remote control setting.
• Outdoor temperature is updated every 30 minutes when operation ON.
12.1.5.1. Heating Mode Operation Time Chart
1. 3 ways valve control:
• 3 ways valve switch and fix to heating side
2. Heat pump operate follow normal heating operation.
3. Backup heater operate follow normal operation.
4. Solar 3 way valve operates follow solar operation specification.
12.1.6. Water Temperature Thermo Shift Setting
• Switchs are ignored during "PUMPDW" = ON.
• Switchs are ignored during "STATUS" = ON.
• "
", "
", "SELECT" switch are ignored if "SETTING" = OFF.
• "CANCEL" switch is ignored if "SETTING" = OFF & "STATUS" = OFF.
• If "SET" Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
Example
48

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxf12d6e5

Table of Contents